4CH Alarm Output Digital Indicator : SC1400 / SC2400

SC1400 and SC2400 Indicators have a Micro Processor. The model apply for proper performance. 4CH Relay Output is possible.(A1~A4 have each point of contract) Easy setting by click the front button, it is possible to set Alarm, full scale values, the decimal point and Calibration. When power outages it retains its data.

 

Feature
Input Signal: 1~3mV/V(SC1400), V or mA(SC2400)
SETTING LED & DISPLAY LED
Max Readout : ±19999
Auto Zero Point Setting
Analog Output : 0, 1~5V, 10V, 4~20mA(DIP S/W)
Function: Data Hold, Peak Hold, Reset 
Frequency Filter : 1, 10, 100Hz(DIP S/W)
48mm×96mm Aluminum Case

 

  SC1400 SC2400
Sensor
Sensor Excitation
Sensor Supply Current
Sensor Output

Sensor Impedance
5VDC
Max 120mA
1~3mV/V(DIP S/W Adjust)

120 or 350Ω

24VDC(3~28VDC Adjust)
MAX 100mA(24VDC)
0~5,1~5V,0~10VDC
4~20mA(DIP S/W Adjust)
-
Analog
Input Impedance

Frequency Filter
Response Frequency
Analog Output
ZERO, SPAN Adjustment
SHORT Protection Circuit
Thermal Effect
More than 5MΩ mA Input 250Ω
V Input More than 5kΩ
1, 10, 100Hz, 4kHz
Max 5kHz
0~5VDC, 1~5VDC, 0~10VDC, 4~20mA(DIP S/W Adjust)
ZERO, SPAN VR Adjust
Internal SHORT Protection Circuit 
0.02%FS/℃
Digital
A/D Sampling Time
A/D Resolution
Max Readout
Height of Digits
Linearity
Decimal point Setting
Display Type
15 or 30 or 120 times/sec
±4½ Digit
±19999
14mm(H)×8mm(W)
±0.02%FS
Be Able to set number of 3 decimal by front switch
7 SEGMENT LED
General
RELAY Output
Electrical Connection
Power
Storage Temperature
Operating Temperature
Mounting Type
Size
Weight
4CH Alarm A point of contract (AC250V/5A, DC30V/5A)
SCREW TERMINAL Connection
AC110(50~60Hz), AC220V(50~60Hz) 
-40~80℃ 
0~50℃ 
Panel 
96(W)×48(H)×110(D) 1/8DIN
570g
Option

Sensor Output :
Less than, 0.75mV/V,
More than 3.5mV/V
Sensor Power : ±15VDC
NPN OPEN COLLECTOR TR S/W Output

 

 

 

 

Cr. : http://www.sensys.co.kr