Flow sensor : TS-FK12

Construction

- Full transmitter in 12mm housing!

- One transmitter type for different piping sizes

- Output signal proportional to media flow rate

- 4…20mA; 0…10V; frequency output; switch or pulse output available

- Adjustable working range

- User configuration by connection pin (teach-in)

- Simplest handling

 

Description

The sensor TS-FK12 is designed for monitoring of non-viscous liquids; monitoring of gaseous media upon request. The sensor and its entire electronics are mounted into a compact size sensor housing of 12 mm diameter equipped with M12x1 round plug connector. Calorimetric signal temperature compensation and linearization are adopted by the built-in 16-bit processor. (Flowing media heat transfer measuring at the sensor tip)

 

The TS-FK12 electronics outputs the measuring result as: 

Analog 0/4…20mA signal (TS-FK12-I)

Analog 0/2…10V signal (TS-FK12-U)

Frequency signal (TS-FK12-F)

Switch signal (TS-FK12-S)

Flow signal pulse/ x litre (TS-FK12-C)

 

The range value can be adjusted by “teach-in” on pending flow upon wishing so.

 

Handling

The measuring range / switching value (TS-FK12-S) can be user set by “teach-in” as described below:

- Set the flow to the maximum flow rate

- Apply a pulse of at least 0.5 sec. and max. 2 sec. to pin 2 (e.g. by installing a bridge to auxiliary voltage or via a pulse from the SPS control) to accept the measured final value

- LED flashes during programming process; in normal mode this LED indicates operation voltage

- After teach-in, pin 2 should be connected to 0 V in order to avoid unintentional programming Attention: The programming function must be stated when ordering; otherwise a non-programmable type will be supplied.

 

 

cr : http://www.tival-sensors.com/products.html