Level control TS-NIA control module for TS-MPS

For liquids, must be used with float switch (i.e. TS-MPS)

Description

- Monitoring and control of 1 to 6 liquid levels

- 3 operating modes: Filling, emptying and level monitoring

- Number of reed-modules adjustable to scale

- 5 LEDs for liquid levels display

- Adjustable time delay (0..30s) for compensation of wave motion

Mode of operation

The level control TS-NIA must be used with a float switch (i.e. TS-MPS). Number of reed-modules in the float switch has to be equal to the number of liquid levels to be monitored. Float switch and level control are forming a functional unit. If the number of reed-modules set to the control unit marked „MODULES“ differs from the number of the actual installed reed-modules in the float switch, the 5 LEDs (N1 to N5) will conjointly flash after supply voltage is connected. No function will be delivered. After setting the right number of modules to the control unit the proper function will be provided immediately. The level control TS-NIA can be comfortably set to one of the three different working modes -filling, emptying and level monitoring- by using a front-mounted turn-knob. The depictable performance of the level control depends on the selected working mode as well as on the number of reed-modules installed in the float switch. Level monitoring feature, displayed by yellow LEDs, is available independently from the working mode set to the level control. Important notice: Prior to initial use, the floater must be moved one time fully up and down the float pipe to assure safe level readout!

 

 

cr : http://www.tival-sensors.com/products.html