48mm X 96mm Panel Mounting Differential Ultra Low Pressure Gauge / Switch : DPA
DPA model is ideal for the application (such as HVAC) with differential pressure, vacuum pressure, gauge pressure and especially low pressure of non-corrosive gases or air measured. Device for Ultra Low Pressure Gauge / Switch, which is using MICOM, improved Accuracy and Temperature compensation.
Features
CE Certified
4 digit LED display
48mm X 96mm Panel Mounting Type
Pressure Unit selection(Pa, mmH2O, mbar)
Auto Zero
2-channel Relay Alarm output
1~5, 0~5, 0~10, 10~0VDC, 4~20mA analog output
Measuring range 0~50..1000Pa diff.
0.5..1%FS accuracy
Piezoresistive silicon cell
Use with non-corrosive, non-ionic media
Applications
Airflow Measurement
Room Static Pressure
VAV Box
Lab/Fume Hood Control
Clean Room Control
Range | 0~50,100,200Pa ±50,±100,±200Pa |
0~300,500,750,1000Pa ±300Pa,±500,±750,±1000Pa |
Performance Accuracy Thermal Effect(Zero) Thermal Effect(Span) Compenated Temp. Operating Temp. |
±1%FS±1digit ±0.1%FS/℃ ±0.1%FS/℃ |
±0.5%FS±1digit ±0.05%FS/℃ ±0.05%FS/℃ |
0~50℃ -10~70℃ |
||
Electrical Display Excitaton Output Switching Signal Analog Signal Electrical Connection |
4 Digit FND 18~26VDC 2-Channel Relay (5A 28VDC / 10A 125VAC / 5A 250VAC) 1~5, 0~5, 0~10, 10~0VDC, 4~20mA Terminal |
|
Physical Proof Pressure Burst Pressure Vibration Shock Pressure Port Wetted Materials |
300%FS Max. 500%FS Min. 49.1m/s2{5G}, 10~500Hz 490m/s2{50G} 1/8", 3/16" Nipple BsP, SiO₂, Si Rubber |
Cr. : http://www.sensys.co.kr