Compact Size Differential Pressure Transmitterr, Applied for HVAC : DPD

DPD model is ideal for the application (such as HVAC) with differential pressure, vacuum pressure, gauge pressure and especially low pressure of non-corrosive gases or air measured. Analog output 4~20mA, 2wire and it provides LCD display.

Features
3 1/2 digit LCD display
2Wire 4~20mA analog output
Measuring range 0~300...100kPa diff.
0.5%FS accuracy
Piezoresistive silicon cell
Use with non-corrosive, non-ionic media

Applications
Airflow Measurement
Room Static Pressure
VAV Box
Lab/Fume Hood Control
Clean Room Control

 

Range 0~300, 500Pa / 1, 2, 5, 10, 20, 50, 100kPa (Diff.)
Performance
Accuracy
Thermal Effect on Zero
Thermal Effect on Span
Compenated Temp. Range
Operating Temp. Range 
±0.5%FS ± 1digit
±0.08%FS/℃
±0.08%FS/℃
0~50℃
-10~70℃
Electrical
Display
Exitation
Output
Electrical Connection
±1999(3 1/2) Digit LCD
14~28VDC
4~20mA (2Wire)
Cable
Physical
Proof Pressure
Burst Pressure
Vibration
Shock
Pressure Port
Media-Wetted Materials
Weight
300%FS Max.
500%FS Min.
49.1m/s2{5G}, 10~500Hz
490m/s2{50G}
1/8" Nipple
BsP, SiO2, Si Rubber
Approx. 150g

 

 

 

Cr. : http://www.sensys.co.kr