L100 Bubble Tube Liquid Level System

Precision Transmission of Liquid Level in Open Tanks.

L100 Bubble Tube Liquid Level System

Precision Transmission of Liquid Level in Open Tanks

The Dahl L100 Bubble-Tube Level System is a fully self contained instrument, requiring only connections to air or gas supply, dip tube and electrical power source to provide precise level indication. Because only the stationary dip tube and the purge gas come in contact with the liquid, this system is ideal for applications involving hazardous locations or liquids which are highly corrosive, viscous, hot, (molten metal), explosive, slurry type or floodstuff. In addition, the electronic output from the L100 is compatible with almost all analog instrumentation, including local and remotely-located indicators, computers, data loggers, recorders and controllers.

Specifications

Ranges

0-50 inches water to 0-115 feet water or equivalent, full scale

Gas Input

1.0 to 7.0 SCFH, regulated on-board to a pressure between 120% or 3 psi, whichever is greater, and 200% of full scale liquid head. Maximum blow-down pressure is 150 psi. Maximum on-board regulated pressure is 60 psi

Electrical Input

Using P200: 10-42 VDC

Electrical Output

P200: 2 wire, 4-20mA into 700Ħ at 24 VDC or 2 wire, 10-50mA into 280Ħ at 24 VDC

Accuracy

±0.25% of span guaranteed; ±0.20% of span typical. Includes combined effects of linearity, hysteresis and repeatability errors.

Sensitivity

±0.02% of span guaranteed

Repeatability

±0.10% of span max; ±0.05% of span typical

Operating Temperature

30°F to 161°F

Thermal Sensitivity

Span: 0.007% of span per °F guaranteed
Zero: 0.007% of span per °F guaranteed 

RFI/EMI Effect

Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter

Environmental

P/I is NEMA 4X and explosion proof, standard. Entire plate assembly fits in an optional NEMA 4X enclosure for further protection.

Available Options

NEMA 4X enclosure with or without digital readout, remote analog readout, auto purge

Ordering Information

The following ordering codes are sufficient to specify a complete bubble-tube system with the exception of the P/I transducer. The P/I transducer must be ordered separately. Please refer to ControlAir's specifications for the Dahl P200 P/I Transducer.

Assemblies

Ordering Code Description
L100 Basic bubble-tube system
L100R Basic system with remote pressure sensing
L100A Basic system with automatic blow-down
L100AR Basic system with remote pressure sensing and automatic blow-down

For a NEMA 4X Enclosure, add suffix E to end of part number. For a 4X enclosure with window and digital readout, add suffex EW to end of part number. Example: L100RE.

Ranges

Ordering Code Description
L11 0-50" WC to 0-166" WC, specify
L12 0-167" WC to 0-498" WC, specify
L13 0-499" WC to 0-830" WC, specify
L14 0-831" WC to 0-1384" WC, specify

Options

Ordering Code Description
L22 Digital readout, scaled for range*

*Analog readout available as P200 option P27 When ordering, it is necessary to specify the model number, range and all options in the following manner:

L100REW + L12
System with 
remote sensing 
in NEMA 4X enclosure
with window and
digital readout
+
Range, specify 
0-322” WC

The P/I transducer must be ordered separately. Please refer to ControlAir’s specifications for the ControlAir P200 P/I Transducer.

 

 

Cr : http://www.controlair.com/