T5500 Multi-station, Digital-to-Pneumatic Pressure Regulator with DeviceNet™ or Profibus™
T5500 Multi-station, Digital-to-Pneumatic Pressure Regulator with DeviceNet™ or Profibus ™
4, 6, or 8 station air pressure control from a common air supply
This multi-station manifold uses a common air supply to provide electronic proportional control of output pressure from any combination of 4, 6, or 8 station units through the use of a DeviceNet™ or Profibus™ communication network. An 8-bit digital signal describing the required output pressure for each electronic regulator is sent by DeviceNet™ or Profibus™ to the T5500 node. The T5500 converts the digital signal into the appropriate 4-20mA signal that is sent to each corresponding I/P transducer which adjusts output pressure to the desired setting. An optional pressure sensor feeds back a diagnostic signal by DeviceNet™ or Profibus™ to the controller, which then monitors pressure output from each I/P.
Specifications
Functional Specifications
Input |
DeviceNet™ or Profibus™ | |
Power Supply | 24 Volts | |
Outputs |
3-15 psig, 3-27 psig, 6-30 psig, 2-60 psig, 3-120 psig | |
Air Consumption |
1.8 scfh per station at mid range typical |
|
Supply Pressure |
100 psig max. for 3-15, 3-27, 6-30 psig units 150 psig max. for 2-60, 3-120 psig units |
|
Flow Capacity |
4.5 scfm at 25 psig supply (3-15, 3-27, 6-30 psig) 12.0 scfm at 100 psig supply (3-15, 3-27, 6-30, psig) 20.0 scfm at 150 psig supply (2-60, 3-120 psig) |
|
Relief Capacity | 2.0 scfm at 5 psig above set point | |
Temperature Limits |
-20° to +150° F |
Performance Specifications
Linearity/Hysteresis & Repeatability |
<0.5% of span |
|
Supply Pressure Sensitivity |
<0.1% of span per 1.0 psig change |
|
RFI/EMI Effect |
<0.5% |
Physical Specifications
Media |
Clean, dry, oil-free, air, filtered to 40 micron |
||||||
Port Sizes |
|
||||||
Electrical |
|
||||||
Mounting |
Wall or DIN Rail |
||||||
Weight |
|