Type 595XP Explosion-Proof I/P Transducer
Type 595XP Explosion-Proof I/P Transducer
High level of regulation accuracy and repeatability for the operation of actuated valves
The Type-595XP Explosionproof I/P (current to pressure) transducer converts a 4–20mA electrical current signal to a proportionally linear pneumatic output. The unique conversion technology utilizing open loop control provides a high level of accuracy and repeatability for the operation of actuated valves. A low mass control circuit provides consistent output in high vibration applications.
This compact unit is housed in an explosion proof enclosure that is designed for pipe, bracket or direct manifold mounting. This explosion-proof and intrinsically safe field device is available with an integral volume booster or as a low-flow signal converter that directly mounts to a pneumatic valve positioner. The Type-595XP has worldwide agency approvals for use in hazardous areas.
Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available. The ControlAir Type-925 Multifunction Manifold provides a common supply port and individual shutoff valves for sets of 3, 5, 10 or 15 units.
Specifications
Functional Specifications
|
P Connection (with Flow Booster) |
M & N Connection (without Flow Booster) |
||||||||||||
Inputs |
|
|
||||||||||||
Outputs |
|
|
||||||||||||
Air Consumption |
0.1 scfm (0.17m3/hr) |
2.00 scfh (0.06 m3/hr) @ 4.94 scfh (0.14 m3/hr) @ 8.36 scfh (0.24 m3/hr) @150 psig supply (10.0 BAR) |
||||||||||||
Supply Pressure |
|
|
||||||||||||
Flow Capacity |
2.4 scfm (4.1 m3/hr)max. |
Same as Air Consumption |
||||||||||||
Temperature Limits |
-67°F to 185°F (-55°C to 85°C) |
-67°F to 185°F (-55°C to 85°C) |
||||||||||||
Relative Humidity |
75% average - 95% short time non-condensing |
75% average - 95% short time non-condensing |
||||||||||||
Impedance |
260 Ohms @ 70°F | 260 Ohms @ 70°F | ||||||||||||
Loop Load |
5.2 Volts @ 70°F | 5.2 Volts @ 70°F |
Performance Specifications
|
STANDARD RANGE |
ZERO-BASED RANGE |
Linearity (Independent) |
<± 0.5% of span |
<± 0.5% of span |
Hysteresis |
<±0.3% of span |
<±0.3% of span |
Deadband | <±0.1% of span | <±0.1% of span |
Repeatability | <±0.3% of span; <±0.15% of span typical |
<±0.3% of span; <±0.15% of span typical |
Mounting Orientation Effect |
<±0.5% / 90 degree change |
<±0.5% / 90 degree change |
Air Supply Sensitivity |
<.3% / 1.5 (0.10 BAR) psig change |
<±0.6% / 25 (1.72 BAR) psig change |
Vibration Effect |
<±1% up to 10g |
<±1% up to 10g and 20-80 Hz |
Temperature Effect |
<±0.75% / 10°F (5.6°C) change |
<±0.75% / 10°F (5.6°C) change |
Physical Specifications
Housing |
NEMA 4X (IP 65) |
||||
Port Sizes |
|
||||
Media |
Clean, dry, oil-free, instrument air, filtered to 40 micron |
||||
Electrical Connections |
Terminal block |
||||
Mounting |
Direct (standard) or 2" pipe (optional) | ||||
Mounting
|
Housing: Chromate-treated aluminum with epoxy paint. NEMA 4X (IP65) Elastomers: Buna-N Trim: Stainless steel; brass; zinc-plated steel |
||||
Weight |
P version=1.40 lbs (0.64 kg) N version=1.25 lbs (0.57 kg) |