Counter/Timer : LE4S Series

DIN W48×H48mm Digital backlight LCD Timer

DIN W48×H48mm Digital backlight LCD Timer

Upgraded back light type digital LCD timers LE4S/LE4SA are downsized by approx. 22% saves mounting space and adopted the new design nameplate. In addition, it is available to set each value and time range separately when choosing Flicker(FK, FK I) or ON-OFF Delay(ON OFF D, ON OFF D I) output mode. New LE4S/LE4SA's upgraded powerful functions of wide variety would fully satisfy customers’ needs.

Main features
* Mounting space saving with compact design
 : downsized by approx. 22% in depth compared to existing models (Length of panel on the back side is 56mm)
* Available to set each value and time range separately when choosing Flicker(FK, FK I) or ON-OFF Delay(ON OFF D, ON OFF D I) output mode (existing model: setting value only)
* Add Flicker 1 mode (LE4SA)
* Set One-shot output time (0.01~99.99sec) (existing model : Fixed 0.5 sec)
* Time range is configurable (time setting range to 9.999sec) : Able to set to 0.001sec (existing model : 0.01sec)
* Choose Min. input signal : 1ms or 20ms (existing model: Fixed 20ms) (LE4S)
* Improved return time: 100ms (existing model : 300ms, 500ms)
* Back light ON/OFF function
* Providing more easy function setting modes
* Wide time range
* Lock setting function for saving setting value.
* Function setting with soft touch
* High visibility display with back light
* Wide range of power supply: 24-240VAC 50/60Hz, 24-240VDC


Applications

 

Ordering Information

 

Specification Table

Model LE4S  LE4SA
Function Multi time and operation
Display method LCD dlsplay(Backlight)
Power supply 24-240VAC 50/60HZ, 24-240VDC
Allowable voltage range 90 to 110% of rated voltage
Power consumption 24-240VAC: Max. 4.5VA, 24-240VDC: Max. 2W 24-240VAC: Max. 4VA, 24-240VDC: Max. 1,6W
Return time Max. 100ms
Min. input signal START 1ms, 20ms(Selectable) -
INHIBIT
RESET
Input START • No-voltage input
Impedance at short-circuit : Max. 1㏀,
Residual voltage : Max. 0.5V,
Impedance at open-circuit : Min. 100㏀
-
INHIBIT
RESET
Timing operation Signal ON start Power ON start
Control output Contact type Time limit SPDT(1c) Time limit DPDT(2c), Time limit SPDT(1c)+
Instantaneous SPDT(1c) : Selectable
Contact capacity 250VAC 5A resistive load 250VAC 3A resistive load
Relay life cycle Mechanical Min. 10,000,000 operations
Electrical Min. 100,000 operations at 250VAC 2A resistive load
Output mode 10 operation modes 8 operation modes
Environ -ment Ambient temperature -10 to 55℃, storage: -25 to 65℃
Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
Repeat error Max. ±0.005% ±0.03sec.(Signal start)Max. ±0.01%
±0.05sec.(Power ON start)
Max. ±0.01% ±0.05sec.
Setting error
Voltage error
Temperature error
Insulation resistance 100MΩ(at 500VDC megger)
Dielectric strength 2000VAC 50/60Hz for 1 minute
Noise strength ±2kV the square wave noise(pulse width : 1㎲) by the noise simulator
Vibration Mechanical 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 1hour
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10 minutes
Shock Mechanical 300m/s²(30G) in each of X, Y, Z directions for 3 times
Malfunction 100m/s²(10G) in each of X, Y, Z directions for 3 times
Approval CE,UL
Unit weight Approx. 98g

※Environment resistance is rated at no freezing or condensation.  


Dimensions

 

Connections

User's Guide

 

Caution for your safety

Cr. : http://www.autonics.com/