Counter/Timer : ATS Series

Wide range of power supply options & set up time all in a slim design

Wide range of power supply options & set up time all in a slim design

ATS Series is a small analog multi-functional timer that allows wide ranges of power supply options and time setting options for users. This series is highly cost efficient and is equipped with a vast range of output operation modes. Also, this series gives freedom of options to users by adopting 37 different types within the line-up including Star-Delta, Power-off, Delay and Twin timers.

Main features

* Slim size (W38 X H42 X L70mm)
* Wide ranges of power supply and time setting
* Various output operation modes
* Specialized socket PS-M8 with 41mm in width allows close attachment and installation on DIN rail
* Specialized adaptor for DIN 48x48mm allows mounting and installation on panel and provides easy maintenance

 

Ordering Information

Specification Table

• Small Multi Timer

Model ATS8-□1  ATS8-□3 ATS11-□1D ATS11-□3D ATS11-□1E ATS11-□3E
Function Multi Function Timer
Control time setting range 0.1sec to 10hour 0.3sec to 30hour 0.1sec to 10hour 0.3sec to 30hour 0.1sec to 10hour 0.3sec to 30hour
Power supply • 100-240VAC 50/60Hz, 24-240VDC, universal  • 24VAC 50/60Hz, 24VDC, universal  • 12VDC
Allowable voltage range 90 to 110% of rated voltage
Power consumption • 100-240VAC: 4.2VA, 24-240VDC: 2W
• 24VAC: 4.5VA, 24VDC: 2W 
• 12VDC: 1.5W
• 100-240VAC : 3.5VA, 24-240VDC : 1.5W
• 24VAC : 4VA, 24VDC :1.5W 
• 12VDC : 1W
• 100-240VAC : 4.2VA, 24-240VDC : 2W
• 24VAC : 4.5VA, 24VDC : 2W
• 12VDC : 1.5W
Return time Max. 100ms
Min. Input signal width START - Max. 50ms
INHIBIT
RESET
Input START - No-voltage input - Short-circuit impedance : Max. 1㏀,
Residual voltage : Max. 0.5V
Open-circuit impedance : Max. 100㏀
INHIBIT
RESET
Time operation Power ON Start Signal ON Start
Control output Contact type Time limit DPDT(2c) or Instantaneous
SPDT(1c)+Time limit SPDT(1c) selectable according to output operation mode
Time limit DPDT (2c) Time limit SPDT (1c), Instant limit SPDT (1c)
Contact capacity 250VAC 3A resistive load
Relay life cycle Mechanical Min. 10,000,000 operations
Electrical Min. 100,000 operations (250VAC 3A resistive load)
Repeat error Max. ±0.2% ±10ms
Setting error Max. ±5% ±50ms
Voltage error Max. ±0.5%
Temperature error Max. ±2%
Insulation resistance 100Mi!(at 500VDC megger)
Dielectric strength 2000VAC 50/60Hz for 1 min.
Noise resistance ±2kV the square wave noise (pulse width 1㎲) by noise simulator
Vibration Mechanical 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) In each of X, Y, Z directions for 1 hour
Malfunction 0.5mm mplitude at frequency of 10 to 55Hz(for 1 min.) In each of X, Y, Z directions for 10 min.
Shock Mechanical 300m/s2 (30G) in each of X, Y, Z directions 3 times
Malfunction 100m/s2 (10G) in each of X, Y, Z directions 3 times
Environ- ment Ambient temperature -10 to 55°C, storage: -25 to 65°C
Ambient humidity 35 to 85%RH
Approval CE, UL
Unit weight Approx. 72g

※ Environment resistance is rated at no freezing or condensation.


• Small Twin Timer 

Model ATS8W-□1  ATS11W-□1 ATS8W-□3  ATS11W-□3
Function ON/OFF Flicker operation
Control time setting range 0.1sec to 10hour 0.3sec to 30hour
Power supply • 100-240VAC 50/60Hz, 24-240VDC (universal)   • 24VAC 50/60Hz, 24VDC (universal)    • 12VDC
Allowable voltage range 90 to 110% of rated voltage
Power consumption • 100-240VAC : 4.2VA, 24-240VDC : 2W   • 24VAC : 4.5VA, 24VDC : 2W   • 12VDC : 1.5W
Return time Max. 100ms
Time operation Power ON Start type
Control
output
Contact type Time limit DPDT(2c), Instantaneous SPDT(1c)+Time limit SPDT(1c) selectable according to output operation mode
Contact capacity 250VAC 3A resistive load
Relay life
cycle
Mechanical Min. 10,000,000 operations
Electrical Min. 100,000 operatlons(250VAC 3A resistive load)
Repeat error Max. ±0.2% ±10ms
Set error Max. ±5% ±50ms
Voltage error Max. ±0.5%
Temperature error Max. ±2%
Insulation resistance 100㏁ (at 500VDC megger)
Dielectric strength 2000VAC 50/60Hz for 1 min.
Noise resistance ±2kV the square wave noise (pulse width 1㎲) by noise simulator
Vibration Mechanical 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 1 hour
Malfunction 0.5mm mplltude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10 min.
Shock Mechanical 300m/s²(30G) in each of X, Y, Z directions 3 times
Malfunction 100m/s²(10G) in each of X, Y, Z directions 3 times
Environment Ambient temperature -10 to 55℃, storage: -25 to 65℃
Ambient humidity 35 to 85%RH
Approval CE,UL
Unit weight Approx. 72g

※Environment resistance is rated at no freezing or condensation. 


Dimensions

 

Connections

 

User's Guide

 

Caution for your safety

Cr. : http://www.autonics.com/