SMART VALVE POSITIONER : SSR (Rotary Type)

Smartest valve control device meeting a dynamic performance and a precise setting with a piezoelectric technology and an optimized auto-calibration program

Features

- Auto-calibration for optimum conditions
- Precise control performance and high dynamic response
- Easy operation with fork-key pads and full text graphical LCD 
-  Single and double acting 
- Low air consumption due to piezo electric microvalve 
-  Pressure regulator built-in to eliminate variations in supply air pressure 
- Problem-free characteristics on a small actuator
- High resistance against shock and vibration
- Mounting on rotary actuators according to VDI/VDE3845

 

Option 

- Position transmitter (4…20㎃ output signal)
- 2 X alarm limit (Min.,Max.)
- Explosion proof type (Exd IIB T6, Exia IIC T6)
- HART communication (FSK)

 

Specifications 

Input signal

4 – 20㎃ @ 24 VDC

Voltage drop

8.5 VDC @ 20㎃ (425 Ω)

Min./ Max. current

3.6㎃ / 50㎃

Required load voltage
(≒Ω @20㎃)

Without HART : 8.5V (≒ 425 Ω)
With HART : 9.2V (≒ 460 Ω)

Air supply pressure

1.4 - 7.0 bar (20 - 100 psi)
Filtered compressed dry and non-oiled air

Output pressure

0-100% supply air pressure / single or double action

Shut-off valve

Range 0 - 5% of position signal

Air capacity

6.6㎏/h=5.4N㎥/h=3scfm @ supply air of 1.4bar (20psi)

Air consumption

< 0.04kg/h

Humidity limits

< 90% RH, non-condensing

Stroke/Angle   

40 - 90° (Max. up to 100°)

Adjustable speed

1 - 1000 (lowest 1, highest 1000)

LCD indication

4-digit LCD indicator

Scan time

2ms

Valve action

Position 0-100% / direct action (DA) / reverse action (RA)

Characteristic curve

Linear, E.Q.% (1:25 or 1:50), Quick open
Linearity<=0.3% / sensitivity<=0.2% / hysteresis<=0.2%

Operationg temperature

-20 ~ +80℃

Protection class

IP66, intrinsic safety (Exia), flameproof (Exd)

Body material

Aluminum die-cast

Pneumatic connections

Rc 1/4 or 1/4 NPT

Electrical connections

2 X G 1/2 or 1/2 NPT

Weight

2.5kg

 

How to order 

SSR-
Protection Class
Feedback
Shaft
Pressure Gauge(SUP.OUT)
Position Feedback
HART Communication
Connection Threads
Mounting Bracket

Description

Code

Protection class : F : Flameproof (Exd IIB T6) 
I : Intrinsic safety (Exia IIC T6)
W : Weatherproof to IP66
Feedback shaft : F : Fork lever 
N : NAMUR shaft 
     (direct mounting)
Pressure gauge : N : None
1 : 6 bar (90psi)
2 : 10 bar (150psi)
Position feedback : N : None
O : Position transmitter
     (4-20㎃ output signal)
L : 2 X alarm limit
M : O + L

Description

Code

HART communication : N : None
H : HART comm
Connection threads :
(pneumatic-electrical)
3 : Rc 1/4 – G 1/2 (standard)
4 : NPT 1/4 – NPT 1/2
5 : Rc 1/4 – M20 X 1.5
Mounting bracket : N : None 
R : Multi-size Bracket
     for DIN VDI/VDE 3845 
    (130X30X50 Bracket 
     on request)

 

Cr. : http://www.power-genex.com/