Load Cell : LTE Series
Information
LTE series load cells are single ended and made from special alloy steel that isolates it from corrosion and industrial environments. Work with shear beam principle and is nickel plated. LTE type load cells were designed for compression applications. It has IP67 nipple cable and stainless steel cover that enhances environmental protection.
General Applications
- Weighing platfroms
- Bunker weighings
- Silo and tank weighings with low and middle capacities
- Dosing system
- Packaging and filling machines
- Band weighings
Capacity
LTE series load cells are produced in 1,2,5 ton capacities.
Tachnical specification
Type |
LTE |
||
Accuracy class |
C1 |
C3 |
|
Capacity (Emax) |
1-2-5 T |
||
Minimum dead load |
0% R.O |
||
Rated output R.O |
2,0 mV/V |
||
Maximum number of load cell interval Nmax |
1000 |
3000 |
|
Vmin |
Emax/4000 |
Emax/10000 |
|
Emax / Vmin |
4000 |
10000 |
|
Minimum dead load output return (MDLOR) |
<0,0500 %R.O |
<0,0167 %R.O |
|
Zero balance |
1 %R.O |
||
Temperature effect on zero |
<< 0,0070 %R.O/5°C |
||
Temperature effect on output |
< 0,0055 %R.O/5°C |
||
Compensated temperature range |
-10 /+40 °C |
||
Temperature range safe |
-30 /+70 °C |
||
Maximum safe central overload |
150 %R.O |
||
Ultimate central overload |
300 %R.O |
||
Excitation |
5 V |
||
Input impedance |
380±20 Ω |
||
Output impedance |
350±3 Ω |
||
Insulation resistance |
>1000 MΩ |
||
Construction |
Nickel plated alloy steel |
||
Environmental protection |
IP67 |
||
Cable type |
2X2x0,22 mm |
||
Cable length |
5 m |
||
Weight |
1-2T: 2,4kg |