Level Switches : LV10
Switch-Tek™ Vertical Buoyancy Level Switch
Application
The general purpose buoyancy point level switch provides reliable liquid level detection of relatively clean water and chemical solutions with a 15VA reed switch output. Media examples include boric acid and ultrapure water. The baffle body eliminates level switch chatter caused by turbulence. The submersible polypropylene or PVDF liquid level sensor is mounted vertically inside the tank as a high level alarm or low level alarm.
Features
Baffle body and stabilized float dampen out switch chatter
Submersible polypropylene or PVDF sensor and cable for corrosive liquids
15VA dry contact selectable NO or NC state via wiring selection
Compatible with Smart Trak and Switch-Pak installation fittings
Literature
Specifications
Orientation: | ± 20° vertical |
Accuracy: | ± 2mm in water |
Repeatability: | ± 1mm in water |
Specific gravity: | 0.8 minimum |
Contact type: | (1) SPDT reed |
Contact rating: | 15 VA, 0.25A maximum |
Contact output: | Selectable NO / NC |
Process temp.: | F: -40° to 176° C: -40° to 80° |
Pressure: | 25 psi (2 bar) @ 25º C, derated @ 1.667 psi (0.113 bar) per ºC above 25º C |
Sensor rating: | NEMA 6 (IP68) |
Sensor material: | -13X1: PP -53X1: PVDF |
Cable jack. mat.: | -13X1: PP -53X1: PFA |
Cable type: | 3-conductor, shielded |
Cable length: | 10' (3m) |
Process mount: | 3/4" NPT (3/4" Rp) |
Classification: | General purpose |
Compliance: | CE |
Cr : http://flowline.com