Level Transmitters : LU80-84
EchoSpan® Ultrasonic Level Transmitter
Application
The general purpose ultrasonic level transmitter provides continuous level measurement up to 32.8' (10m) with a 4-20 mA signal output, and is configured via its integral push button display module. This non-contact liquid level sensor is ideally suited for corrosive, ultrapure, sticky or dirty liquids, and is broadly selected for bulk storage, day tank, lift station and process tank level applications.
Features
Offered in 4 measurement ranges from 9.8' (3m) to 32.8' (10m)
Configuration is simple via integral push button display module
LCD display indicates level in inches, centimeters and percentages
Narrow 2" or 3" beam width for applications with limited measurement space
Fail-safe intelligence and diagnostic feedback for simple troubleshooting
PVDF transducer and NEMA 4X polycarbonate enclosure for corrosive liquids
Automatic temperature compensation for accurate measurement
Literature
Specifications
Range: | LU80: 4" to 9.8' (10cm to 3m) LU81: 8" to 18.0' (20cm to 5.5m) LU83: 8" to 26.2' (20cm to 8m) LU84: 12" to 32.8' (30cm to 10m) |
Accuracy: | ± 0.2% of range |
Resolution: | LU80: 0.019" (0.5mm) LU81/83: 0.039" (1mm) LU84: 0.078" (2mm) |
Dead band: | LU80: 4" (10cm) LU81/83: 8" (20cm) LU84: 12" (30cm) |
Beam width: | LU80: 2" (5cm) LU81/83/84: 3" (7.6cm) |
Configuration: | Push button |
Memory: | Non-volatile |
Display type: | LCD, 6-digit |
Display units: | Inch, cm and percent |
Supply voltage: | 12-28 VDC |
Loop resist.: | 500 Ohms @ 24 VDC |
Signal output: | 4-20 mA, two-wire |
Signal invert: | 4-20 mA, 20-4 mA |
Signal fail-safe: | 4mA, 20mA, 21mA, 22mA or hold last |
Process temp.: | F: -4° to 140° C: -20° to 60° |
Temp. comp.: | Automatic |
Ambient temp.: | F: -31° to 140° C: -35° to 60° |
Pressure: | MWP = 30 psi (2 bar) |
Enclosure rating: | NEMA 4X (IP65) |
Encl. material: | Polycarbonate |
Encl. hardware: | Brass & stainless |
Enclosure vent: | Water tight membrane |
Conduit entrance: | Dual, 1/2" NPT |
Trans. material: | PVDF |
Process mount: | LU80: 1" NPT (1" G) LU81/83/84: 2" NPT (2" G) |
Mount gasket: | Viton® |
Classification: | General purpose |
Compliance: | CE, RoHS |
Cr : http://flowline.com