Counters/Flow : SPI-73

SPI-73 are the flow meters designed to work in tandem with the pulse flow transducers with coefficients ranging from 0,01 to 9999,99 pulses per litre. Wide range of total flow (up to 15 significant digits) enables flow volume control for a long time. The counters have 1 relay or OC output, which is programming depending on the actual instantaneous value of the flow.

 

Parameters

Input pulse galvanically isolated with contacts oscillation damping, max. frequency from 10 kHz; reset of totalizer counter: edge or level triggered, galvanically isolated
Display LED, red, 6 x 9 mm high
Data memory non-volatile memory, EEPROM type
Displayed values range 0 ÷ 999999 + decimal point
Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
Output 1 relay 1A/250V AC (cos fi=1) or OC 30mA/30VDC/100mW; power supply output: 24V DC + 5% -10% / max 100 mA
Transmission parameters 1200 ÷ 115200 bit/s, 8N1 and 8N2
Communication interface RS-485 / Modbus RTU (not galvanically isolated)
Protection class IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips)
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Case panel mounting
Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (with option 08)
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Accuracy instantaneous flow values: selected in the range 0 ÷ 0,00000; total flow accuracy: selected in the range from ± 1 to ± 0,0001
Panel cut-out dimensions 66,5 x 32,5 mm
Case dimensions 72 x 36 x 97 mm
Instantaneous flow unit l or m3 per second, minute or hour
Instantaneous flow precision selected from range: 0 ÷ 0.00000
Total flow unit I or m3
Pulse waiting time settable from 0,1 do 39,9 seconds
Total flow precision selected from range: 0 ÷ 0.000
Total flow capacity over 4 x 10^9 pulses (max. 16 significant digits)
Installation depth min 102 mm