Indicator : SRP-457

Meter in tight (IP 65 or IP 67), wall mounting case, with large display, current-voltage input, 1 relay (or OC type) output. The version without relay outputs is also available.

 

Parameters

Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 11 VA; 19V ÷ 50V DC power supply: max. 8 W
Display LED, red, 4 x 57 mm, with 8-step adjustment of brighness
Input current 0-20 mA or 4-20 mA, programmable, input resistance < 65 Ohm (typ. 55 Ohm), overload-protected, input current limited to 40 mA; voltage 0-5 V, 1-5V, 0-10V or 2-10V, programmable, input resistance > 50 kOhm
Displayed values range -999 ÷ 9999 + decimal point
Accuracy ± 0,25% ± one digit in the entire operation range
Output 1 relay 1A/250V AC (cos fi=1) or the OC 30mA/30VDC/100mW; transducer power supply output: 24V DC +5%, -10% / max. 100 mA, stabilized, not insulated from measuring inputs
Communication interface RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (not galvanically isolated from measuring inputs)
Protection class IP 65 (standard); IP 67 (option)
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (depending on version)
Case wall-mounted (depends on IP version)
Case dimensions IP65 case: 215 x 185 x 118,2 mm; IP67 case: 230 x 140 x 96,5 mm
Case material ABS + glass fibre
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Stability typ. 50 ppm/°C

 

 

Cr : http://www.simex.pl/en