Parameters
Power supply | 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC |
---|---|
Input | 2, 4 or 8 inputs 0/4-20 mA, common earthing |
Display | with backlighting, graphic LCD, 128 x 64 points |
Displayed values range | ± 9999 + decimal point |
Power consumption | typical 7 VA; max. 12 VA |
Stability | typ. 50 ppm/°C |
Output | 2 electronic relays, NO type (ER1, ER2) with max. load 24V AC (35V DC) / 200 mA, overload protection |
Communication interface | RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (isolated from measuring inputs) |
Case material | NORYL- GFN2S E1 |
Protection class | IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-99; IP 20 (case and connection clips) |
Operating temperature | 0°C ÷ +50°C |
Accuracy | ± 0,25% ± one digit in the entire operation range |
Case | panel mounting |
Storage temperature | -10°C ÷ +70°C |
Panel cut-out dimensions | 90,5 x 90,5 mm |
Case dimensions | 96 x 96 x 100 mm |
Software | The device supports S-Toolkit software - free in "Download" section. |