Indicator : MultiCon CMC-141

 

Parameters

Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Input up to 15 universal inputs; 72 analogue inputs (0/4-20 mA or 0/1-5V or 0/2-10V) max.; 72 digital inputs max.; 36 thermocouple inputs max.; 18 RTD inputs max.; 12 counter/ flowmeter/ ratemeter inputs max.; 1 digital input 24V DC (available in standard, integrated with  PS3 or PS4 power supply module)
Display 5.7 inch graphic TFT, 16-bit colour, 320 x 240 pixels, with touchscreen
Measurement range depends on input
Power consumption typical 25 VA; max. 35 VA
Output 24 analog (4-20 mA) or 36 relay (1A/250V) / 72 SSR outputs or 18 relay 5A/250V max., sensor supply: 24 V DC ± 5% (200 mA max. for current inputs)
Communication interface standard: RS-485 (Modbus RTU), 1 x USB Host; ETU version: 1 or 2 x USB Host, 1 x Ethernet 10 MB; enhanced ACM version: 2 x RS-485, 1 x RS-485/232, 1 or 2 x USB Host, 1 x Ethernet 10 MB
Internal memory capacity 1,5 GB
Available data recording speed from 0,1 s to 24 h with resolution 0,1 s
Case material NORYL - GFN2S E1
Protection class IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-141; version with front USB: IP 40 or IP 54 (when fitted with STD-141 transparent door)
Operating temperature 0°C ÷ +50°C
Case panel mounting
Storage temperature -10°C ÷ +70°C
Case dimensions 144 x 144 x 100 mm
Panel cut-out dimensions 137 x 137 mm
Software Free DAQ Manager software for multichannel controller can be downloaded directly from section „Download”
Installation depth min. 102 mm

 

 

Cr : http://www.simex.pl/en