DUCT HUMIDITY TRANSMITTER : GDHO-420 (¾)
"GDHO" Duct Humidity Transmitter can be used as follows for Ventilation an Air-Handling units.
● Sensing supplying or ventilating air humidity
● Shift sensor (In case of revising room humidity depend on outside air humidity)
● Measuring sensor (Display sensing value or in case of using DDC auto control stsyem)
Technical Data
SUPPLY VOLTAGE | DC15 ~ 30V |
FREQUENCY | 50 or 60Hz |
SENSING ELEMENT | Integrated Circuit |
POWER CONSUMPTION | 0.5VA |
SENSING RANGE | 0 ~ 100%Rh |
ACCURACY at 20℃ | at 20 ~ 90%Rh within ±3% Rh |
OUTPUT SIGNAL | 4 - 20mA DC |
SENSING TIME | within 30 sec (at wind speed 2m/s) |
AMBIENT TEMPERATURE ; 1) On operation 2) On transportation & storage |
-5 ~ 70℃ -35 ~ 80℃ |
AMBIENT HUMIDITY ; 1) On operation 2) On transportation |
5 ~ 100%Rh Below 95%Rh |
CABLE FITTING | PG9 |
Protection degree endosure | IP54 (EN60529) |
Probe Material | SUS304 |
Probe length | 100 mm |
WEIGHT | 0.30Kg.(W/BRACKET) |
Wiring Diagram
Dimension
Cr. : http://www.ginice.co.kr